SVC to improve productivity and power quality in a steel plant fed by a 230 kV grid
Customer Story | 2 min read
SVC to improve productivity and power quality in a steel plant fed by a 230 kV grid
Firstly, the plant wished to run its EAF at a higher power output without risking to infringe on the flicker requirements of the 230 kV power supplier, Bonneville Power Administration (BPA). This would enable an increase of EAF power from 65 MW up to 84 MW, the maximum yield of the furnace in question.
Secondly, the plant wished to lower the overall impact of flicker and harmonics on the transmission supply system, while obtaining an improved power factor at the 230 kV Point of Common Coupling (PCC).
The SVC is rated at 34.5 kV, 0-90 Mvar (capacitive), continuously variable. It has the following tasks:
Main data | |
---|---|
System | SVC |
Commissioning year | 2000 |
Controlled voltage | 34.5 kV |
SVC rating | 0-90 Mvar capacitive
|
Control system | Phasewise, open loop susceptance regulator |
Thyristor valve | BCT equipped, water cooled, with indirect light firing. |